3.3kW Totem-pole PFC with CoolMOS and XMC1402
control_interrupts.c File Reference

Control related interrupts code. More...

#include <DAVE.h>
#include "LLD_conf_code/adc.h"
#include "control_interrupts.h"
#include "init_bckgnd_funct.h"

Functions

void current_loop_ISR (void)
 Current loop interrupt.
CR2 while counting up in CCU80.CC81 (PWM-PFC) triggers the ADC queue.
A result event of the queue triggers this interrupt.
Prio 1. More...
 
void current_ref_ISR (void)
 Current reference interrupt.
pwm_count counts number of PWM cycles.
PR event of pwm_count triggers the current_fed_ISR() at a defined number of switching cycles.
Prio 2. More...
 
void voltage_loop_ISR (void)
 Voltage control interrupt.
Timer CCU40.CC42 triggers this interrupt in the period match event.
IIR low-pass filter of the AC voltage to obtain the RMS value.
IIR notch filter of the DC voltage to remove 100Hz and 120 Hz component.
Voltage loop and voltage monitoring.
State machine for start-up and event management.
Prio 3. More...
 

Variables

static volatile uint8_t i_filter = 0
 
volatile PFC_var_t PFC
 
volatile uint16_t time_count_5kHz = 0
 
static volatile uint16_t current_loop_cnt = 0
 
ADC results
volatile uint32_t * ADCResult_iL
 
volatile uint32_t * ADCResult_DCBus
 
volatile uint32_t * ADCResult_VAC
 
volatile uint32_t * ADCResult_Temp
 
Control and Fault status registers
volatile state_t status_reg = ST_INIT
 
volatile fault_t fault_reg = F_INIT
 

Detailed Description

Control related interrupts code.

Author
Meneses Herrera, David; Escudero Rodriguez, Manuel
Date
28.12.2020
totempole_sensing.png
3300W Bidirectional Totem-pole CCM sensing and ground positioning.


TPPFC_control_concept.png
3300W Bidirectional Totem-pole CCM control structure.